As primary insulation for splicing and repair of solid dielectric insulated cables up to 69 kV, as well as for primary insulation repair in joints and terminations and stress cone construction up to 35 kV. Provides reliable insulation protection for busbars, overhead lead wire, and sheath and jacket repair.
| Available Models | KCJ-23C |
|---|---|
Dimensions (T x W x L) | 0.76 mm x 19 mm x 9,000 mm (0.030" x 0.748" x 29.528') |
| Base Material | EPR |
| Tensile Strength | 1.7 MPa |
| Elongation at Break | 700% |
| Dielectric Strength | 30.0 kV/mm |
| Volume Resistivity | 1 ×1014 Ω·cm |
| Continuous Operating Temperature | 90°C/194°F |
| Emergency Overload Temperature | 130°C/266°F |
(Typical Values)
*Dimensions are customizable upon request.
Abrade and clean the application site before wrapping. Stretch the Linerless Self-Fusing Insulating Tape KCJ-23C to twice its original length, and apply it over the target area in successive, half-lapped, level-wound layers.
Email: info@sinokc.com
Telephone: (+86)-0510-83109661
Address: Building No.1, No.8 Jinshansizhi Rd., Jinshanbei Science & Technology Park, Wuxi, Jiangsu, 214037, China
All statements, technical information, recommendations, and usage related to Wuxi Kuncheng New Material Technology Co., Ltd. are based on reliable information, but accuracy or completeness is not guaranteed. The data and information in this website may not be relevant to all product users.It is the user's responsibility to determine the suitability of the product for its intended application, and the user assumes all risks, injuries, death, and liability associated with such use. Wuxi Kuncheng New Material Technology Co., Ltd. expressly disclaims all express or implied warranties, including merchantability and fitness for a particular purpose to the fullest extent permitted by law and does not accept responsibility or liability, whether direct, indirect, or consequential, arising from use of the product or reliance on this website.